ENS-220100C Acculader
ENS-220100C Acculader
RELIABLE BY DESIGN
ENS-220100C Acculader
Merk:INLANX
Beschrijving: ENS-220100C Acculader
Weerstand, nominaal vermogen, tolerantie, TCR, behuizing, draadlengte, montagemethode, markering en verpakking kunnen allemaal worden aangepast.
Productseries op de site kunnen als alternatief dienen voor EBG, HVR, Vishay en andere merken. Klanten moeten monsters en specificaties controleren voordat zij vervangende modellen op grote schaal gebruiken.
- Grootte
- 605*260*400 mm
- Tolerantie
- ±0.5% / ±0.1% / ±1%
- Serie
- ENS-220100C Acculader
- Merk
- INLANX
Productgegevens
Productbeschrijving
Provides automatic charging, process monitoring and data analysis for battery and UPS maintenance. Supports constant-current, constant-voltage/taper and trickle/float three-stage charging, recording voltage, current, time and capacity. Suitable for charging maintenance of lead-acid and lithium batteries; set operating parameters according to battery requirements.
Technische kenmerken
- Three-stage charging: constant current → constant voltage with tapering current (equalization voltage regulation) → trickle/float; automatically controls charging for lead-acid batteries, lithium batteries and UPS maintenance.
- Automatic termination: stops charging when group or cell voltage reaches the set upper limit, charging time reaches its setting, or charged capacity reaches its setting; records continuous process data.
- Touch operation: 7-inch high-brightness TFT LCD with resistive touchscreen and 1024×600 resolution for direct on-screen operation.
- Wireless cell monitoring (optional): LoRa modules support 2V, 4V, 6V and 12V cells; each module simultaneously monitors 6 cells. The source example uses 4 modules for a 48V battery group.
- Wireless bands: receives and changes wireless cell-monitoring module bands; supports settings 1-10 for multiple instruments in the same equipment room.
- Cell analysis: with cell acquisition modules, displays charging cell voltages as real-time bar charts and data tables, identifying the highest- and lowest-voltage cells.
- Historical curves: reviews recorded battery-group voltage and current curves.
- Charging templates: 6 built-in test templates can be edited and recalled.
- Data management: USB-drive data export, PC software analysis and report generation; test-data names can be edited on the instrument.
- Power-loss recovery: enabled by default; automatically resumes the test state preceding the outage when mains power returns, maintaining continuous test records.
- Online monitoring (optional): requires cell modules and a current clamp; monitors and records battery-group voltage, current, capacity and time, and generates reports.
- Reserved interfaces: RS485 master for cell-voltage acquisition, RS485 slave for remote control, and CAN for signal input/readout. Actual enablement follows the technical specifications.
Technische specificaties
| Charge voltage | 90-270 VDC |
|---|---|
| Charge current | 0-100 A |
| Dimensions (L×W×H) | 605 × 260 × 400 mm |
| Main-unit mass | ≤29.6 kg |
| AC supply | AC 380 V (ABCN+PE), 40-60 Hz |
| Operation | Touchscreen |
| Display | 7-inch TFT LCD, resistive touch, 1024×600 |
| Data communication | RS485×1 (disabled by default) |
| Internal storage | 8 Gbit FLASH |
| Voltage measurement accuracy | ±0.5%FS + 0.1 V |
| Current measurement accuracy | ±1%FS + 0.1 A |
| Group voltage display accuracy | 0.1 V |
| Group current display accuracy | 0.01 A |
| Main-unit protection | Shutdown on overtemperature, overcurrent or loss of current control |
| Shutdown device | High-voltage DC switch |
| Reverse-polarity protection | Supported |
| Abnormal-condition protection | Power loss on the mains cable or main cable |
| Overtemperature thresholds | Resistor enclosure 85°C; heatsink 100°C |
| Alarm | LCD indication and buzzer |
| Cooling | Forced-air cooling |
| Operating temperature | -5 to +50°C |
| Storage temperature | -40 to +70°C |
| Relative humidity | 0-90% RH (40±2°C) |
| Rated altitude | 2000 m |
Toepassingen en selectie