RELIABLE BY DESIGN
12KW-AC/DC-PTC
Merek:INLANX
Deskripsi: INLANX-12KW-AC/DC-PTC Bank beban PTC AC/DC tipe rak: perangkat beban uji tipe rak dengan kepadatan daya tinggi, dirancang khusus untuk kabinet standar 19 inci di pusat data IDC. Pembebanan bertahap: 1KW/1KW/2KW/4KW/4KW.
Resistansi, daya nominal, toleransi, TCR, kemasan, panjang kaki, metode pemasangan, pelabelan, dan pengemasan dapat disesuaikan.
Seri produk di situs ini dapat menjadi alternatif untuk EBG, HVR, Vishay, dan merek lainnya. Pelanggan harus memverifikasi sampel dan spesifikasi sebelum menggunakan model pengganti dalam jumlah besar.
- Ukuran
- 440*178*600 mm
- Daya nominal
- 12000 W
- Toleransi
- ±10%
- TCR
- 400 ppm
- Teknologi
- Bahan resistif PTC
- Seri
- 12KW-AC/DC-PTC Bank beban PTC AC/DC tipe rak
- Merek
- INLANX
Deskripsi: INLANX-12KW-AC/DC-PTC Bank beban PTC AC/DC tipe rak: perangkat beban uji tipe rak dengan kepadatan daya tinggi, dirancang khusus untuk kabinet standar 19 inci di pusat data IDC. Pembebanan bertahap: 1KW/1KW/2KW/4KW/4KW.
Merek:INLANX
Detail produk
Deskripsi produk
Our 12KW-AC/DC-PTC rack-mounted load bank is a high-power-density test load developed specifically for standard 19-inch cabinets in IDC data centers.
Fitur teknis
- Uses PTC resistors that automatically reduce power as temperature rises; internal silicone cables have a temperature rating of ≥150℃.
- • Loading is disabled until the fan starts; at an internal cabinet temperature of 70℃, the load is removed and an audible and visual alarm activates.
- • After overtemperature, confirm power disconnection and reset manually; monitor throughout testing.
- • Disconnect the supply side before the load side when removing cables.
- • Secure all 6 input plugs; use indoors with personnel monitoring throughout testing.
Tabel model
| Model |
|---|
| 12KW-AC/DC-PTC |
Spesifikasi teknis
| AC voltage range | AC192-250V; approximately constant load power |
|---|---|
| DC voltage range | DC192-288V; approximately constant load power |
| Rated power | 12KW |
| Frequency / power factor | 50/60Hz (AC); power factor 1 |
| Power steps | 1KW、1KW、2KW、4KW、4KW |
| Load power deviation | +5% to +10% (positive deviation) |
| Input interfaces | 6 independent C14 sockets at the rear; each rated 10A |
| Power cord | C13-C14; configurable for the site PDU |
| Resistor / internal wiring | PTC; silicone cable rated ≥150℃ |
| Temperature protection | 70℃ inside enclosure; alarm and load disconnect |
| Other protection | Fan interlock, fuse for short circuit/overcurrent, DC contactor |
| Cooling / airflow | Forced-air cooling, front intake and rear exhaust; 1500 m ³ /h |
| Fan voltage | DC24V |
| Cabinet dimensions | Width×height×depth = 440 × 178 × 600 mm |
| Installation / weight | Indoor; 18KG |
| PTC power degradation | ≤ 5% within 1 year; ≤ 8% within 3 years |
Aplikasi dan pemilihan
- Suitable for AC 220V and DC 270V systems to check operation under load of precision air conditioning, power and environment monitoring, distribution, UPS, diesel generation, row distribution cabinets and PDU supply systems.