AC-8KW-R resistive load bank (rack load)
AC-8KW-R resistive load bank (rack load)
RELIABLE BY DESIGN
AC-8KW-R resistive load bank (rack load)
Brand: INLANX
Description: INLANX-AC-8KW-R resistive load bank (rack load) uses alloy resistance material, which is characterized by stable power and small temperature drift. When used as a load, the power is stable and fully meets the test requirements. It is currently widely used at home and abroad. Used as load and heating materials. 500W/500W/1KW/2KW/2KW/2KW loading in batches
Resistance, power rating, tolerance, TCR, package, lead length, mounting method, and labeling and packaging can all be customized.
Product series across the site can serve as alternatives to EBG, HVR, Vishay and other brands. Customers must verify samples and specifications before using replacement models in volume.
- Size
- 430*177*550 mm
- Rated power
- 8000 W
- Tolerance
- ±10%
- TCR
- 250-400ppm
- Technology
- Metal tube / wirewound
- Series
- AC-8KW-R resistive load bank (rack load)
- Brand
- INLANX
Product details
Product description
Our AC-8KW-R rack load bank is designed for 19-inch standard racks in IDC equipment rooms, for AC 220V systems as a simulated load below 8KW. It tests precision air conditioning, monitoring and power supply systems in equipment rooms under load.
Technical features
- 500W/500W/1KW/2KW/2KW/2KW stepped loading
- Alloy resistors with stable power and low temperature drift
- Fan interlock: loading requires the fan to be on
- 70°C overtemperature unloading and audible/visual alarm
- Internal silicone cables withstand over 120°C
- 19-inch standard cabinet, 4U rack mounting
Technical specifications
| Rated voltage | AC220V |
|---|---|
| Rated power | 8KW |
| Frequency | 50HZ/60HZ |
| Power factor | 1 |
| Load resistor accuracy | ≤ 5% |
| Fan model | DC24V, 15050 |
| Air flow | 1000 m ³ /h |
Applications and selection
- Simulated load tests check load capability and wiring reliability throughout the electrical chain from distribution equipment and diesel generators to UPS, row distribution cabinets and PDU; precision air conditioner operation as aisle or equipment-room temperature rises; UPS battery switching under load and supply duration; diesel generator starting under load and power supply; and other simulated load tests.