4U5KW-AC220V-R AC rack load bank
4U5KW-AC220V-R AC rack load bank
RELIABLE BY DESIGN
4U5KW-AC220V-R AC rack load bank
Brand: INLANX
Description: INLANX-4U5KW-AC220V-R AC rack-mounted load bank is a high-power density rack-mounted test load device specially designed and developed for the 19-inch standard cabinet environment of IDC data centers. 500W/1KW/1.5KW/2KW loading in stages
Resistance, power rating, tolerance, TCR, package, lead length, mounting method, and labeling and packaging can all be customized.
Product series across the site can serve as alternatives to EBG, HVR, Vishay and other brands. Customers must verify samples and specifications before using replacement models in volume.
- Size
- 485*177*500 mm
- Rated power
- 5000 W
- Tolerance
- ±5%
- TCR
- 300ppm℃
- Technology
- Metal tube / wirewound
- Series
- 4U5KW-AC220V-R AC rack load bank
- Brand
- INLANX
Product details
Product description
Our 4U5KW-AC220V-R rack load bank is a high power density rack test load designed for the 19-inch standard rack environment of IDC data centers.
Technical features
- Nickel-chromium alloy resistors provide low temperature drift, high melting point and corrosion resistance for stable load power. Internal high-temperature silicone cables withstand over 120℃; overtemperature protection is set to 70℃. The fan and load are interlocked: loading requires the fan to be on; overtemperature disconnects load power and triggers audible and visual alarms.
Technical specifications
| Rated voltage | AC220V |
|---|---|
| Rated power | 5KW |
| Power steps | 500W, 1KW, 1.5KW, 2KW |
| Weight | 15KG ± 0.5KG |
| Load accuracy | ≤ 5% |
| Load input | Four rear C14 sockets in parallel; each rated 10A |
| Enclosure dimensions | W × D × H = 485 × 500 × 177 mm |
| Operating ambient temperature | Below 70℃ (protection setting) |
| Cooling method | Forced air cooling (front intake, rear exhaust) |
Applications and selection
- Verify load capability and wiring reliability of the entire electrical chain: distribution equipment, diesel generators, UPS, row distribution cabinets and PDU.
- Check precision air conditioning operation as aisle or equipment room temperature rises.
- Test UPS switching under load and supply duration.
- Test diesel generator starting under load and power supply capability.
- For other simulated load tests.