ENS-3805DC Intelligent Integrated Battery Charge/Discharge Unit

RELIABLE BY DESIGN

ENS-3805DC Battery Charge/Discharge Unit

Brand: INLANX

Description: ENS-3805DC Intelligent Integrated Battery Charge/Discharge Unit. Please refer to the uploaded datasheet for detailed technical specifications and operating conditions.

Resistance, power rating, tolerance, TCR, package, lead length, mounting method, and labeling and packaging can all be customized.

Product series across the site can serve as alternatives to EBG, HVR, Vishay and other brands. Customers must verify samples and specifications before using replacement models in volume.

Size
725*265*500mm
Tolerance
±0.5% / ±0.1% / ±1%
Technology
PTC
Series
ENS-3805DC Intelligent Integrated Battery Charge/Discharge Unit
Brand
INLANX

Product details

Product description

For battery-group charge/discharge, activation and maintenance testing; records group and cell voltages, charge/discharge current, time and capacity to assess energy-storage performance and load capacity.

Technical features

  • Load source: custom nickel-chromium alloy resistors with low resistance and high power density; resistance accuracy can be controlled within ±0.001 Ω; low temperature coefficient and resistance to high-current surges.
  • Intelligent control: adjusts the load as battery voltage changes to maintain constant-current discharge; acquires cell voltages in real time, displays curves and analyzes voltage status, with multiple configurable assessment thresholds.
  • Discharge testing: supports constant-current or constant-power discharge through the internal load with the battery group offline, or constant-current discharge in parallel with user equipment. Voltage, current, time and capacity thresholds are configurable; discharge parameters can be changed during testing.
  • Discharge termination: stops testing at the group cutoff voltage, capacity or time limit, when any cell voltage falls below its configured lower limit, or on manual termination; records group voltage, cell voltages, current, time and discharged capacity.
  • Automatic charging: uses three stages, constant current → constant voltage with tapering current (equalization voltage regulation) → automatic transition to trickle/float charging, for battery charging recovery and maintenance.
  • Touch operation: 7-inch high-brightness TFT resistive touchscreen with 1024×600 resolution and direct on-screen operation.
  • Wireless cell monitoring (optional): LoRa modules support 2V, 4V, 6V and 12V cells; each module monitors 6 cells simultaneously. The source example is a 48V battery group fitted with 4 modules.
  • Cell-data analysis: displays cell voltages in real time during charging and discharging, supports bar charts and data tables, and automatically identifies the highest- and lowest-voltage cells to help analyze trends.
  • Curves and reports: allows review of battery-group voltage and current curves; supports USB-drive data transfer, with analysis software parsing data and generating reports.
  • Cycle activation: automatically switches an offline battery group to charging after discharge completes, without manual switching.
  • Charge termination: stops automatically when group or cell voltage reaches the configured upper limit, charging time reaches the configured value, or charging capacity reaches the configured value, and records process data.
  • Wireless-band settings: the main unit receives and modifies the bands of wireless cell-monitoring modules, supporting up to 1-10 band settings for multiple instruments in the same equipment room.
  • Test templates: 6 built-in charge/discharge test templates can be edited and recalled; test-data names can be edited on the main unit for record management.
  • Discharge modes: constant current, constant power and constant voltage are supported as standard.
  • Compensated discharge (optional): requires an external current clamp. The main unit automatically adjusts the internal load according to the current measured by a Hall sensor to maintain constant-current battery-group discharge. Displayed current=battery-group current=internal discharge current+actual load current.
  • Parallel testing (optional): supports multiple main units connected in parallel in master/slave mode; requires a master/slave communication cable.
  • Power-loss recovery: enabled by default. After a mains interruption during discharge, charging or cycle activation testing, automatically resumes the previous test state when power returns, maintaining continuity of testing and recording.
  • PC control: supports parameter settings and start/stop control through host-computer software.
  • Internal-resistance testing: wireless cell-monitoring modules allow measurement of each cell''s internal resistance and coefficient adjustment; measurement results are for reference.
  • Online monitoring (optional): requires cell modules and a current clamp; monitors and records battery-group voltage, current, capacity and time, and supports report generation.
  • Reserved communication interfaces: RS485 master interface for cell-voltage acquisition; RS485 slave interface for remote control; reserved CAN interface for signal reading. Actual interface enablement follows the parameter table.

Technical specifications

Discharge voltage90-450 VDC; compatible with 110V, 220V, 380V battery groups
Discharge current0-50 A, continuously adjustable
Charge voltage90-450 VDC; compatible with 110V, 220V, 380V battery groups
Charge current0-50 A
Power limitsmaximum charge power 20 kW
Dimensions (length × width × height)725 × 265 × 500 mm
Main-unit mass≤37.3 kg
AC supplyAC 380 V (ABCN+PE), 40-60 Hz
OperationTouchscreen
Display7-inch TFT LCD, resistive touch, 1024×600
Data communicationRS485×1 (disabled by default)
Internal storage8 Gbit FLASH
Voltage measurement accuracy±0.5%FS + 0.1 V
Current measurement accuracy±1%FS + 0.1 A
Group voltage display accuracy0.01 V
Group current display accuracy0.01 A
Discharge current control accuracy±1%FS
Main-unit protectionShutdown on overtemperature, overcurrent or loss of current control
Shutdown deviceHigh-voltage DC switch
Reverse-polarity protectionSupported
Abnormal-condition protectionPower loss at the power cable or main cable
Overtemperature thresholdsResistor enclosure 85°C; heatsink 100°C
AlarmLCD indication and buzzer
CoolingForced-air cooling
Operating temperature-5 to +50°C
Storage temperature-40 to +70°C
Relative humidity0-90% RH (40±2°C)
Rated altitude2000 m

Applications and selection

  • Suitable for battery and UPS power-supply maintenance.