INLANX
English

No customer account required. Enquiries and sample requests use guest forms.

Products
‹

80KW-AC380V AC resistance load bank

80KW-AC380V AC resistance load bank

RELIABLE BY DESIGN

80KW-AC380V AC resistance load bank

Brand: INLANX

Description: INLANX-80KW-AC380V 80KW AC resistance load bank is made of nickel-chromium alloy material, which is characterized by very small temperature drift, high melting point and corrosion resistance. When used as a load, the power is stable and fully meets the test requirements. It is mainly used as a simulated load when testing the load capacity and other electrical performance of the generator or UPS.

Resistance, power rating, tolerance, TCR, package, lead length, mounting method, and labeling and packaging can all be customized.

Product series across the site can serve as alternatives to EBG, HVR, Vishay and other brands. Customers must verify samples and specifications before using replacement models in volume.

Size
650*1300*850 mm
Rated power
80KW
Tolerance
±10%
TCR
400ppm℃
Technology
Nickel-chromium alloy
Series
80KW-AC380V AC resistance load bank
Brand
INLANX

Product details

Product description

Our high-power AC load bank serves as a simulated load for testing generator or UPS load capacity and other electrical performance.

Technical features

  • The load bank uses nickel-chromium alloy resistors with very low temperature drift, a high melting point and corrosion resistance. They provide stable load power to meet testing needs and are widely used domestically and internationally as load and heating materials.
  • Internal wiring uses high-temperature silicone cable rated above 120℃, which does not burn at high temperatures. The protection temperature is set to 70℃. A fan interlock prevents loading when the fan is off. Excessive temperature disconnects load power and triggers audible and visual alarms.
  • The load bank provides comprehensive protection and contains multiple resistor modules. Different load powers can be selected for different test objects to evaluate their electrical performance.

Technical specifications

Rated voltageAC380V
Rated power80KW
Power stages (three-phase AC)1KW,2KW,2KW,5KW,10KW,15KW,15KW,30KW
Power factor1
Load accuracy≤ 5%
Fan supplyAC220V
Load connectionQuick connectors
Enclosure dimensionsW*H*D=650*1300*850
Operating ambient temperatureBelow 70 degrees (set protection temperature)
CoolingForced air cooling (front intake, rear exhaust)

Applications and selection

  • As a simulated load, test load capacity and wiring reliability throughout the electrical chain from substation/distribution equipment and diesel generators to UPS, row distribution cabinets and PDU.
  • As a simulated load, check whether precision air conditioning meets requirements as aisle or equipment-room temperature rises.
  • As a simulated load, test UPS transfer capability under load and power-supply duration.
  • As a simulated load, test whether diesel generators can start and supply power normally under load.
  • Other simulated-load tests.

Available models

1 modelsApplied filters

All models

ImagePart / SeriesBrandDatasheetResistancePackagePower WTolerance %TCR ppmTechnologyStockLead timeEnquiry
80KW-AC380V AC resistance load bank80KW-AC380V 80KWINLANX650*1300*850 mm80000 W±10%400 ppmNickel-chromium alloy100