RELIABLE BY DESIGN

6U16KW-AC220V-R

Brand: INLANX

Description: INLANX-6U16KW-AC220V-R AC rack-mounted load bank is a high-power density rack-mounted test load equipment specially designed and developed for the 19-inch standard cabinet environment of IDC data center. 500W, 500W, 1KW, 2KW, 4KW, 4KW, 4KW step-by-step loading

Resistance, power rating, tolerance, TCR, package, lead length, mounting method, and labeling and packaging can all be customized.

Product series across the site can serve as alternatives to EBG, HVR, Vishay and other brands. Customers must verify samples and specifications before using replacement models in volume.

Total stock: 1,000

Size
430*266*550 mm
Rated power
16000 W
Tolerance
±10%
TCR
400 ppm
Technology
Metal tube / wirewound
Series
6U16KW-AC220V-R AC rack load bank
Brand
INLANX

Description: INLANX-6U16KW-AC220V-R AC rack-mounted load bank is a high-power density rack-mounted test load equipment specially designed and developed for the 19-inch standard cabinet environment of IDC data center. 500W, 500W, 1KW, 2KW, 4KW, 4KW, 4KW step-by-step loading

Total stock: 1,000

Brand: INLANX

Product details

Product description

Our 6U16KW-AC220V-R rack load bank is designed for standard 19-inch rack environments in IDC data centers.

Technical features

  • Alloy resistors provide stable power and low temperature drift; internal silicone cables withstand temperatures above 120℃.
  • Loading is disabled until the fan starts. Overtemperature triggers audible and visual alarms and disconnects the load. Manual reset is permitted only after power-off is confirmed.

Technical specifications

Rated voltageAC220V / AC240V
Rated power / frequency16KW; 50Hz / 60Hz
Power stages500W、500W、1KW、2KW、4KW、4KW、4KW
Power factor / resistance tolerance1; ≤ 5%
Control supplyAC220V
Load input8 rear C14 sockets in A/B/C/D groups; each rated 10A
Wiring requirementsBoth sockets in each group must connect to the same phase; branch A must be powered
Supplied power cordsAs specified in the contract
Operating environment / temperature protectionIndoor; below 70℃ (protection temperature)
Protection and interlockShort-circuit protection; overtemperature audible and visual alarm and unloading; loading disabled until the fan starts; manual reset after power-off
Cooling / airflowForced air cooling, front intake and rear exhaust; 2000 m ³ /h
Fan informationDC24V, 20060
Resistor / internal wiringAlloy resistors; silicone cable rated above 120℃
Enclosure dimensionsWidth×height×depth = 430 × 266 × 550 mm; bent and welded steel sheet with electrostatic surface coating
Weight15KG

Applications and selection

  • For AC220V / AC240V systems and simulated loads below 16KW, to check precision air conditioning, monitoring, power supply, UPS, diesel generation, racks and PDU under load.
  • Test the load capacity and wiring reliability of AC distribution equipment, diesel generators, UPS, row distribution cabinets and PDU.
  • Simulate load heating to check precision air-conditioning operation.
  • Test UPS battery supply duration under load and diesel-generator starting and supply under load.