RELIABLE BY DESIGN
ENS-220100C
Marca:INLANX
Descrizione: ENS-220100C Caricabatterie
Resistenza, potenza nominale, tolleranza, TCR, contenitore, lunghezza dei terminali, metodo di montaggio, marcatura e imballaggio possono essere personalizzati.
Le serie di prodotti presenti sul sito possono costituire alternative a EBG, HVR, Vishay e altri marchi. I clienti devono verificare campioni e specifiche prima di usare i modelli sostitutivi in quantità.
Disponibilità totale:100
- Dimensione
- 605*260*400 mm
- Serie
- ENS-220100C Caricabatterie
- Marca
- INLANX
Descrizione: ENS-220100C Caricabatterie
Disponibilità totale:100
Marca:INLANX
Dettagli del prodotto
Descrizione del prodotto
Provides automatic charging, process monitoring and data analysis for battery and UPS maintenance. Supports constant-current, constant-voltage/taper and trickle/float three-stage charging, recording voltage, current, time and capacity. Suitable for charging maintenance of lead-acid and lithium batteries; set operating parameters according to battery requirements.
Caratteristiche tecniche
- Three-stage charging: constant current → constant voltage with tapering current (equalization voltage regulation) → trickle/float; automatically controls charging for lead-acid batteries, lithium batteries and UPS maintenance.
- Automatic termination: stops charging when group or cell voltage reaches the set upper limit, charging time reaches its setting, or charged capacity reaches its setting; records continuous process data.
- Touch operation: 7-inch high-brightness TFT LCD with resistive touchscreen and 1024×600 resolution for direct on-screen operation.
- Wireless cell monitoring (optional): LoRa modules support 2V, 4V, 6V and 12V cells; each module simultaneously monitors 6 cells. The source example uses 4 modules for a 48V battery group.
- Wireless bands: receives and changes wireless cell-monitoring module bands; supports settings 1-10 for multiple instruments in the same equipment room.
- Cell analysis: with cell acquisition modules, displays charging cell voltages as real-time bar charts and data tables, identifying the highest- and lowest-voltage cells.
- Historical curves: reviews recorded battery-group voltage and current curves.
- Charging templates: 6 built-in test templates can be edited and recalled.
- Data management: USB-drive data export, PC software analysis and report generation; test-data names can be edited on the instrument.
- Power-loss recovery: enabled by default; automatically resumes the test state preceding the outage when mains power returns, maintaining continuous test records.
- Online monitoring (optional): requires cell modules and a current clamp; monitors and records battery-group voltage, current, capacity and time, and generates reports.
- Reserved interfaces: RS485 master for cell-voltage acquisition, RS485 slave for remote control, and CAN for signal input/readout. Actual enablement follows the technical specifications.
Specifiche tecniche
| Charge voltage | 90-270 VDC |
|---|---|
| Charge current | 0-100 A |
| Dimensions (L×W×H) | 605 × 260 × 400 mm |
| Main-unit mass | ≤29.6 kg |
| AC supply | AC 380 V (ABCN+PE), 40-60 Hz |
| Operation | Touchscreen |
| Display | 7-inch TFT LCD, resistive touch, 1024×600 |
| Data communication | RS485×1 (disabled by default) |
| Internal storage | 8 Gbit FLASH |
| Voltage measurement accuracy | ±0.5%FS + 0.1 V |
| Current measurement accuracy | ±1%FS + 0.1 A |
| Group voltage display accuracy | 0.1 V |
| Group current display accuracy | 0.01 A |
| Main-unit protection | Shutdown on overtemperature, overcurrent or loss of current control |
| Shutdown device | High-voltage DC switch |
| Reverse-polarity protection | Supported |
| Abnormal-condition protection | Power loss on the mains cable or main cable |
| Overtemperature thresholds | Resistor enclosure 85°C; heatsink 100°C |
| Alarm | LCD indication and buzzer |
| Cooling | Forced-air cooling |
| Operating temperature | -5 to +50°C |
| Storage temperature | -40 to +70°C |
| Relative humidity | 0-90% RH (40±2°C) |
| Rated altitude | 2000 m |
Applicazioni e selezione
- Suitable for charging maintenance of lead-acid and lithium batteries; set operating parameters according to battery requirements.